KWE P/N 394038 Versatronik 505 and 505D BACIP Gateway V1.2 February 2014 Technical information subject to change without notice
Mounting Versatronik Gateway—120VAC Unit
2
3
Installation
1. Mount Versatronik 505 Gateway in a
convenient location near the connected boiler
controls control. Remove cover by loosening
the two screws on either side of base to
release the cover.
2. Fasten base to wall using field-supplied
screws/fasteners.
3. Remove knockout and installed wire strain
relief or box connector. Removal of remaining
knockouts is required to make further
connections.
4. Once all of the 120VAC and low voltage
connections are complete and verified, reinstall
the cover from Step 1.
!
When extending wire there is the possibility of
exposure to electromagnetic interference. Avoid
running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage
conductors cannot be avoided, use stranded, twisted
pair of shield design wire. Ensure that only one end of
the shielding is grounded.
Mounting Steps
1
4
1