Viessmann VITOTRONIC 100 GC1B Betriebsanleitung

Stöbern Sie online oder laden Sie Betriebsanleitung nach Warmwasserbereiter & Kessel Viessmann VITOTRONIC 100 GC1B herunter. Viessmann VITOTRONIC 100 GC1B Operating instructions Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 168
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen

Inhaltsverzeichnis

Seite 1 - Installation and

VITOTRONIC 100Installation andservice instructionsfor heating engineersVitotronic100TypeGC1Digital boiler control unitSee applicability, page168.58

Seite 2 - Safety instructions

10Heating system designsSystem version 1 (cont.)Possible applicationsHeating systems with distributorinstalled close to the boiler. Theboiler water vo

Seite 3 - Safety instructions (cont.)

100CommissioningCarrying out a user check (in conjunction with the LON system)Communication with the system devices connected to the fault manager ist

Seite 4

101CommissioningMatching the coding addresses to the system versionIn code 2, set the following coding addresses:Code 2 see page 141."00" Sy

Seite 5 - Index (cont.)

102CommissioningMatching the coding addresses to the system version (cont.)Matching the control unit to a two−stage burner1. Start up the burner.2. Se

Seite 6 - Product information

103CommissioningMatching the coding addresses to the system version (cont.)Matching the control unit to a modulating burnerNoteThe burner must be full

Seite 7 - Summary of system versions

104CommissioningMatching the coding addresses to the system version (cont.)AddressSetting of08 Units and tens of the determined maximum output; e.g. m

Seite 8 - System version 1

105CommissioningChecking outputs (actuators) and sensors (cont.)The following relay outputs can be controlled subject to system design:Display indicat

Seite 9

106Service scansService level summaryFunction Entry Exit PageUser check inconjunction with aLON systemPress L and dsimultaneously for approx.2sPress

Seite 10 - System version 1 (cont.)

107Service scansTemperatures, boiler coding card and brief scans1. Press K and G simultaneouslyfor approx. 2s.Entering the diagnostics level.2. Selec

Seite 11 - System version 2

108Service scansTemperatures, boiler coding card and brief scans (cont.)Brief scansF8 8 8 8 8 80N/A LON user number SoftwareversionCommunic−ationscopr

Seite 12 - System version 2 (cont.)

109Service scansScanning operating conditions1. Press c.Scanning operating conditions isactive.2. Select the required operatingcondition scan with a o

Seite 13

T2T1C CBA90414014314652120A1317A17B2911Heating system designsSystem version 2Raising the return temperature with a shunt pumpVitogas 100Vitomax 100, V

Seite 14 - System version 3

110Service scansScanning operating conditions (cont.)Display indicationDescription NotesP PHoursrun,burner(stage2) The hours run can bee009572h,(g

Seite 15 - System version 3 (cont.)

111Service scansScanning and resetting maintenance displaysAfter limits set up via coding addresses "1F", "21" and "23"

Seite 16 - System version 4

112TroubleshootingFaults which are displayed at the programming unitThe red fault indicator flashes for every fault.A fault code flashes in the displa

Seite 17 - System version 4 (cont.)

113TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedy0fControl mode Maintenance"

Seite 18

114TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedy58Cylinder primarypump ON: Set c

Seite 19 - System version 5

115TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedy92Control modeOnly solar control

Seite 20 - System version 5 (cont.)

116TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause RemedyaaControl mode ThermControlconf

Seite 21

117TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedyb1Control mode Communicationerro

Seite 22 - System version 6

118TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedyc4Control mode Communicationwith

Seite 23 - System version 6 (cont.)

119TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause RemedyceControl mode Communicationfaul

Seite 24

12Heating system designsSystem version 2 (cont.)Required coding02 : 2 Modulating burner operation*103 : 1 Oil fired operation (irreversible)*10d : 

Seite 25 - System version 7

120TroubleshootingFaults which are displayed at the programming unit (cont.)LON users fault messagesOnly if the control unit is the fault manager (cod

Seite 26 - System version 7 (cont.)

121TroubleshootingFaults which are displayed at the programming unit (cont.)FaultcodeSystemcharacteristicsCause Remedy99Control mode Fault message act

Seite 27

122Function descriptionBoiler water temperature controlBrief descriptionThe boiler water temperature isregulated by controlling thetwo−stage or modula

Seite 28 - System version 8

123Function descriptionBoiler water temperature control (cont.)FunctionsThe boiler water temperature isrecorded by three sensorsseparately, which are

Seite 29 - System version 8 (cont.)

124Function descriptionCylinder temperature control (only for single boiler systems)Brief descriptionThe cylinder thermostat operateswith a constant t

Seite 30

125Function descriptionCylinder temperature control (only for single boiler systems) (cont.)Control sequenceH The cylinder primary pump runs onafter c

Seite 31 - System version 9

126Function descriptionCylinder temperature control (only for single boiler systems) (cont.)Code "55:2":Cylinder temperature control with 2

Seite 32 - System version 9 (cont.)

127ComponentsComponents from the parts listFor parts list, see page 153.Main PCB 230 V~The main PCB comprises:H Relays and outputs for controllingpump

Seite 33 - System version 10

128ComponentsComponents from the parts list (cont.)Programming unitSetting the:H Heating programH Set valuesH CodingDisplaying:H TemperaturesH Operati

Seite 34 - System version 10 (cont.)

129ComponentsComponents from the parts list (cont.)TEST keyFor testing the high limit safetycut−out.For a description, see page 98.Control thermostatH

Seite 35 - System version 11

13Heating system designsSystem version 2 (cont.)Possible applicationsHeating systems with distributorinstalled close to the boiler. Theboiler water vo

Seite 36 - System version 11 (cont.)

130ComponentsComponents from the parts list (cont.)Boiler water temperature sensor and cylinder temperature sensorConnectionSee page 66.Checking senso

Seite 37 - System version 12

131ComponentsComponents from the parts list (cont.)Contact temperature sensor and immersion temperature sensorFor recording the return temperature.Con

Seite 38 - System version 12 (cont.)

132ComponentsFlue gas temperature sensor, part no. 7450 630The sensor records the flue gas temperature and monitors the set limit.ConnectionSee page 6

Seite 39 - System version 13

133ComponentsBoiler coding cardTo match the control unit function to the boiler (see page 60).Function extension 0−10V, part no. 7174718To default a

Seite 40 - System version 13 (cont.)

134ComponentsFunction extension 0−10V (cont.)Boiler system withFunction Condition at VitotronicVitotronic100 Demands to the boilerin accordance with

Seite 41 - System version 14

135ComponentsPlug−in adaptor for external safety equipment, part no. 7143 526For the connection of external safety equipment to DIN 4751−2H Low water

Seite 42 - System version 14 (cont.)

CCCX6BGFB B BAX5X4150X1EX8150X2D150X3D150X7D654321654321ONONTRTRNONONTRTRNONONTRTRNONONTRTRN136ComponentsPlug−in adaptor for external safety equipment

Seite 43

137ComponentsVitoair draught stabiliser, part no. 7338 725 and 7339 703A To the burnerB To the control unitColour coding to DIN IEC60757BK blackGN/Y

Seite 44 - System version 15

138ComponentsMotorised flue gas damper, part no. 9586 973 and 9586 974When connecting, remove jumper"TR"  "ON/TR".A To control un

Seite 45 - System version 15 (cont.)

139CodingResetting codes to the delivered condition1. Press L and G simultaneouslyfor approx. 2s, until the first twoarrows appear in the display.2.

Seite 46

14Heating system designsSystem version 3Raising the return temperature with shunt pump and three−way mixerVitogas 100Vitomax 100, Vitomax 200 and Vito

Seite 47 - System version 16

140CodingCode 1 (cont.)Coding in the delivered conditionPossible changeBoiler/burner02:1 Two−stage burner02:0 Single stage burnerg02:2 Mod

Seite 48 - System version 16 (cont.)

141CodingCode 2Calling up code 21. Press L and G simultaneouslyfor approx. 2s, until the first twoarrows appear in the display;confirm with d.Access

Seite 49

142CodingCode2 (cont.)Coding in the delivered conditionPossible changeBoiler/burner (cont.)04:*1Switching hysteresis 04:0 Switching hysteresis

Seite 50 - System version 17

143CodingCode2 (cont.)Coding in the delivered conditionPossible changeBurner (two−stage/mod.) (see page 102) (cont.)09:*1Maximum burner outputin kW

Seite 51 - System version 17 (cont.)

144CodingCode2 (cont.)Coding in the delivered conditionPossible changeBoiler/burner (mod.) (see page 103)15:10 Actuator operating time10s15:5

Seite 52

145CodingCode2 (cont.)Coding in the delivered conditionPossible changeBoiler/burner23:0 No time interval for burnermaintenance23:1to23:24A

Seite 53

146CodingCode2 (cont.)Coding in the delivered conditionPossible changeBoiler2d:0 Shunt pump controlfunction only ON if boiler isenabled2d:1 S

Seite 54

147CodingCode2 (cont.)Coding in the delivered conditionPossible changeDHW55:0 Cylinder heating,hysteresis±2.5K55:1 Adaptive cylinder heati

Seite 55

148CodingCode2 (cont.)Coding in the delivered conditionPossible changeDHW (cont.)61:1 The cylinder primary pumpstarts immediately61:0 The cyl

Seite 56

149CodingCode2 (cont.)Coding in the delivered conditionPossible changeGeneral76:0 Without communicationmodule76:1 With LON communicationmodul

Seite 57 - Installation

15Heating system designsSystem version 3 (cont.)Required coding02 : 2 Modulating burner operation*103 : 1 Oil fired operation (irreversible)*10C : 

Seite 58

150CodingCode2 (cont.)Coding in the delivered conditionPossible changeGeneral (cont.)98:1 Viessmann system number(in conjunction withmonitoring o

Seite 59

151CodingBurner switching hysteresisSwitching hysteresis 4 K (04:0)Heat−demand dependent switching hysteresis (only with outside temp. sensor)ERB50 fu

Seite 60

152Coding5862730GB

Seite 61

153Parts listParts listWhen ordering spare partsQuote the part no. and serial no. (seetype plate A) as well as the item no.of the required parts (as p

Seite 62

154Parts listParts list (cont.)5862730GB015051 018 074 001001013 008031030011037006004042 043065024092025038005

Seite 63

155Parts listParts list (cont.)5862730GB049 016050067 071056068A013014054052014

Seite 64

156Connection and wiring diagramsSummary5862730GB

Seite 65 - Conversion to 100 or 110 ºC

157Connection and wiring diagramsSummary (cont.)A2 Main PCB low voltageA3 Main PCB 230 V~A6 Programming unitA7 Optolink/emissions test switch PCBA8 El

Seite 66 - Sensor connection

158Connection and wiring diagramsMain PCB low voltage5862730GBA11A8A9A6A7A2A1022.5V5.7V

Seite 67 - Pump connection

159Connection and wiring diagramsMain PCB low voltage (cont.)§ Boiler water temperaturesensor% Cylinder temperature sensor(accessories) / cylindertemp

Seite 68

16Heating system designsSystem version 4System with Therm−ControlVitoplex 100, type SX1, to 460kW, Vitoplex 200, type SX2, to 560kW, and Vitoplex 30

Seite 69

160Connection and wiring diagramsMain PCB 230V~5862730GBF1250V6.3A(slow)F2250V6.3A(slow)

Seite 70

161Connection and wiring diagramsMain PCB 230V~ (cont.)sÖ Switching outputorPrimary pump, cylinder storagesystemorCirculation pump, fluegas/water hea

Seite 71

162SpecificationSpecificationRated voltage: 230 V~Rated frequency: 50 HzRated current: 2 (6) A ~Power consumption: 5 WSafety class: IProtection level:

Seite 72

163Keyword indexKeyword indexAAC burner connection,89Actuators,68Actuators, checking,104Adaptive cylinder heating, 125, 147Additional function for

Seite 73

164Keyword indexKeyword index (cont.)DDanger,2DHW heating, 124Diagnostics, 112Draught stabiliser, Vitoair, 137EElectrical connections, 57Electronics

Seite 74

165Keyword indexKeyword index (cont.)MMain PCB230V~,127,160Main PCB low voltage,127,158Mains isolator requirements,94Maintenance display,H Rese

Seite 75

166Keyword indexKeyword index (cont.)SSafety, 2Safety equipment, 84, 135Safety assembly,127Scanning, 107Scanning actual temperatures, 109Scanning ope

Seite 76

1675862730GB

Seite 77

Viessmann Werke GmbH&Co KGD35107 AllendorfTel: +49 6452 700Fax: +49 6452 702780www.viessmann.deViessmann LimitedHortonwood 30, TelfordShrops

Seite 78

17Heating system designsSystem version 4 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 79

18Heating system designsSystem version 4 (cont.)Possible applicationsHeating systems with distributorinstalled close to the boiler. Theboiler water vo

Seite 80

17A17B3C CA90414014314620A1BA52 A1T2T12917A17B390414014314620A152 A1T2T12919Heating system designsSystem version 5Raising the return temperature for e

Seite 81

2Safety instructionsSafety instructions ¨Please follow these safety instructions closely to prevent accidents andmaterial losses.Safety instructions e

Seite 82

20Heating system designsSystem version 5 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 83

21Heating system designsSystem version 5 (cont.)Possible applicationsHeating systems with distributorinstalled close to the boiler. Theboiler water vo

Seite 84

17A317BC CA904140143146BA52 A1T129T217A390414014314652 A1T120A120A122Heating system designsSystem version 6Raising the return temperature with a commo

Seite 85

23Heating system designsSystem version 6 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 86

24Heating system designsSystem version 6 (cont.)Possible applicationsHeating systems with distributorinstalled close to the boiler. Theboiler water vo

Seite 87 - Making the LON connection

C17ACA3904140143146BA52 A117A390414014314652 A1T1 T125Heating system designsSystem version 7Distribution pump and low pressure distributorVitogas 100V

Seite 88

26Heating system designsSystem version 7 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 89 - Pressure−jet oil/gas burners

27Heating system designsSystem version 7 (cont.)Possible applicationsIf the distributor is located in remotesub−stations (> 20 m). The heattransfer

Seite 90

C17ACA3904140143146BA52 A117A390414014314652 A1T1 T128Heating system designsSystem version 8Distribution pump and injection controlVitogas 100Vitomax

Seite 91 - Atmospheric burner

29Heating system designsSystem version 8 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 92 - T6 T7 T8

3Safety instructionsSafety instructions (cont.)If you smell flue gas¨DangerFlue gas can lead tolife−threatening poisoning.H Shut down the heatingsyste

Seite 93

30Heating system designsSystem version 8 (cont.)Possible applicationsIf the distributor is located in remotesub−stations (>20 m), and the heatingci

Seite 94 - Power supply

C17ACA3BA90414014314652 A12917A390414014314652 A129T1 T131Heating system designsSystem version 9Raising the return temperature with a three−way mixing

Seite 95

32Heating system designsSystem version 9 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade cont

Seite 96 - Opening the control unit

C17ACA3BA90414014314652 A12917A390414014314652 A129T1 T1D33Heating system designsSystem version 10Raising the return temperature with a low loss heade

Seite 97 - Controls and display elements

34Heating system designsSystem version 10 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 98

ADC CB390414014314652114314652135Heating system designsSystem version 11System with Vitocrossal 300A Boiler with Vitotronic 100B DHW cylinderC Heating

Seite 99

36Heating system designsSystem version 11 (cont.)Required coding02 : 2 Modulating burner operation*10d : 0 Without Therm−ControlAutomatic changeover

Seite 100 - 5862730GB

C DB3904140143146521143146521orFEAG37Heating system designsSystem version 12Several heating circuits and one low temperature heating circuitVitocrossa

Seite 101

38Heating system designsSystem version 12 (cont.)Required coding02 : 2 Modulating burner operation*10d : 0 Without Therm−ControlAutomatic changeover

Seite 102

AD3904140143146143146C CB52 A1156AD390414014314614314652 A115639Heating system designsSystem version 13Several heating circuits and one low temperatur

Seite 103

4IndexIndexGeneral informationProduct information 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 104 - Relay test

40Heating system designsSystem version 13 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 105 - Checking sensors

AD3904140143146143146C CBA17A390414014314652 A141Heating system designsSystem version 14Several heating circuits and one low temperature heating circu

Seite 106 - Service level summary

42Heating system designsSystem version 14 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 107

43Heating system designsSystem version 14 (cont.)Possible applicationsThe cascade and cylinder controlmust be provided by a higher controlunit.The Vit

Seite 108 - F8 8 8 8 8 8

AD3904140143146143146C CBA17A17B390414014314652 A1T2T12944Heating system designsSystem version 15Several heating circuits, one low temperature heating

Seite 109 - Scanning operating conditions

45Heating system designsSystem version 15 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 110 - 0 0 2 8 5 0

46Heating system designsSystem version 15 (cont.)Possible applicationsThe cascade and cylinder controlmust be provided by a higher controlunit.The Vit

Seite 111

AD3904140143146143146BA17A390414014314629C C47Heating system designsSystem version 16Several heating circuits, one low temperature heating circuit plu

Seite 112

48Heating system designsSystem version 16 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 113

49Heating system designsSystem version 16 (cont.)Possible applicationsFor heating circuits with temperaturedifferentials y 20 K.The cascade and cylind

Seite 114

5IndexIndex (cont.)Service scansService level summary 106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 115

AD3904140143146143146BC CA17A390414014314652 A129T150Heating system designsSystem version 17Three−way mixing valve, several heating circuits and one l

Seite 116

51Heating system designsSystem version 17 (cont.)Codes must be set on every Vitotronic 100.Required coding01 : 2 Multi−boiler system with cascade con

Seite 117

52Heating system designsSystem version 17 (cont.)Possible applicationsFor heating circuits with temperaturedifferentials y 20 K.The cascade and cylind

Seite 118

B552A120A121 17BAC2853System extensionDHW heating with a cylinder storage systemOnly in conjunction with single boiler systemsA Boiler with Vitotronic

Seite 119

54System extensionDHW heating with a cylinder storage system (cont.)Required coding4C : 1 Primary pump connection on plug sÖA14E : 1 Motor connecti

Seite 120 - LON users fault messages

55System extensionSystem with flue gas/water heat exchangerWith shunt pumpWith boiler circuit pump5862730GBABCHABCDEEDFFGGABCHABCDDGGKLLK

Seite 121

56System extensionSystem with flue gas/water heat exchanger (cont.)A Boiler with Vitotronic100B Vitotrans333 (flue gas/waterheat exchanger)C Circula

Seite 122 - Brief description

57InstallationSummary of electrical connections5862730GB150145171753/215143146BA9041151A1/M1A1/M1295040156156215220

Seite 123 - Control sequence

58InstallationSummary of electrical connections (cont.)Main PCB low voltage§ Boiler water temperaturesensor% Cylinder temperature sensorCylinder tempe

Seite 124

59InstallationInserting cables and applying strain reliefInstalling the control unit on the boilerRoute cables from below through the front panel of t

Seite 125

6General informationProduct informationThis document describes Vitotronic 100 when used H in a single boiler system andH in a multi−boiler system with

Seite 126

60InstallationInserting the boiler coding cardOnly use the boiler coding card included with the boiler.BoilerCoding card Part no.Vitocrossal 300, type

Seite 127

61InstallationChanging the high limit safety cut−out setting (if required)The high limit safety cut−out is supplied with a factory setting of 120 ºC.!

Seite 128

62InstallationChanging the high limit safety cut−out setting (cont.)Conversion to 110 or 100 ºC (make T&G)5862730GB1.3.2.4.

Seite 129 - Control thermostat

63InstallationChanging the high limit safety cut−out setting (cont.)Change to 110 or 100 ºC make EGOA Slotted screw1. Release the safety assembly andp

Seite 130

64InstallationChanging the high limit safety cut−out setting (cont.)Conversion to 110 or 100 ºC, make JUMO1. Release the safety assembly.2. Remove res

Seite 131

65InstallationChanging the control thermostat setting (if required)Conversion to 100 or 110 ºCIn the delivered condition, the control thermostat is se

Seite 132

66InstallationSensor connectionA Temperature sensor T2 or Temperature sensor  cylinderstorage systemB Therm−Control temperaturesensor or temperature

Seite 133 - Boiler coding card

67InstallationPump connectionAvailable pump connectionssÖ Cylinder primary pump orCirculation pump  flue gas/water heat exchangersA Cylinder primary

Seite 134

68InstallationConnecting an actuator with three−point outputUse as:H Butterfly valve H Mixer motorH Three−way mixing valve|Open~ClosedRated voltage:

Seite 135

69InstallationExternal hook−up in single boiler systemsOperation with a two−stage burnerZero volt contacts of the highercontrol unit:Burner stage 1 ON

Seite 136

7Heating system designsSummary of system versionsBoiler Characteristics PageSingle boiler systems1 Vitoplex ThermControl 82Vitogas, Vitomax,Shunt p

Seite 137

70InstallationExternal hook−up in single boiler systems (cont.)Starting burner stage 1Contact closed:Burner stage 1 is started. Burnerstage 2 will onl

Seite 138 - STB N STB TR TR

71InstallationExternal hook−up in single boiler systems (cont.)Low temperature boileroperation with a modulating burnerConnection modulating burner

Seite 139 - Calling up code 1

72InstallationExternal hook−up in single boiler systems (cont.)Control unit settingsCode"01:1"(delivered condition)Code"02:1"

Seite 140 - Code 1 (cont.)

73InstallationExternal hook−up in single boiler systems (cont.)Vitocrossal300operation with a modulating burnerConnection modulating burner:H Burn

Seite 141 - Overview

74InstallationExternal hook−up in single boiler systems (cont.)Control unit settingsCode"01:1"(delivered condition)The boiler water tempe

Seite 142 - Code2 (cont.)

75InstallationExternal hook−up in multi−boiler systems without LONOperation with a two−stage burnerZero volt contacts of the highercontrol unit:Burner

Seite 143

76InstallationExternal hook−up in multi−boiler systems without LON (cont.)Starting burner stage 1 and 2Contact closed:Both burner stages are switched

Seite 144

77InstallationExternal hook−up in multi−boiler systems without LON (cont.)Low temperature boiler operation with a modulating burnerConnection modula

Seite 145

78InstallationExternal hook−up in multi−boiler systems without LON (cont.)Zero volt contacts of the higher control unitwith modulation controller:Enab

Seite 146

79InstallationExternal hook−up in multi−boiler systems without LON (cont.)Adjustments on every control unitSet code"01:3"code"02:

Seite 147

8Heating system designsSystem version 1System with Therm−ControlVitoplex 100, type SX1, up to 460 kW, Vitoplex 200, type SX2, up to 560kWand Vitoplex

Seite 148

80InstallationExternal hook−up in multi−boiler systems without LON (cont.)Vitocrossal300operation with a modulating burnerConnection modulating bu

Seite 149

81InstallationExternal hook−up in multi−boiler systems without LON (cont.)Zero volt contacts of the higher control unitwith modulation controller:Enab

Seite 150

82InstallationExternal hook−up in multi−boiler systems without LON (cont.)Adjustments on every control unitSet code"01:3".The high limit

Seite 151 - Burner switching hysteresis

83InstallationExternal hook−up in multi−boiler systems with LONZero volt contacts of the highercontrol unit:Boiler blockingStart boiler as lastone in

Seite 152

84InstallationExternal connections on plug aBÖ !Please note’Live’ contacts lead to short circuits or phase failure.The external connections must be ze

Seite 153 - Parts list

85InstallationExternal connections on plugaBÖ (cont.)!Please noteConnecting an external controlunit can damage the boiler.Connect only safety shutdow

Seite 154 - Parts list (cont.)

86InstallationPlugging in the LON communication module (if required)Plug in the LON communicationmodule in accordance with theillustration in the cont

Seite 155

87InstallationMaking the LON connectionThe Viessmann LON system is designed for "Line" BUS topology, i.e. withterminators at both ends.Conne

Seite 156

88InstallationMaking the LON connection (cont.)Connection withH Viessmann LON cable,H on−site cable andH Viessmann socketfor extensions up to 900 m lo

Seite 157 - Summary (cont.)

89InstallationConnecting an AC burnerPressure−jet oil/gas burnersConnect the burner in accordance with the DIN 4791 or local regulations.The burner ca

Seite 158 - Main PCB low voltage

9Heating system designsSystem version 1 (cont.)Required coding02 : 2 Modulating burner operation*103 : 1 Oil fired operation (irreversible)*10d : 1

Seite 159 - Main PCB low voltage (cont.)

90InstallationConnecting an AC burner (cont.)A To control unitB To burnerTerminal codesT6, T8 Control chainBurner stage 2 ONorModulation controller op

Seite 160 - Main PCB 230V~

91InstallationConnecting an AC burner (cont.)Atmospheric burnerThe burner cables are included in the standard boiler delivery.Max. power consumption 6

Seite 161 - Main PCB 230V~ (cont.)

92InstallationConnecting a three−phase burner  zero volt safety chain!Please noteA jumper in the burner may possibly have to be removed from theexter

Seite 162 - Specification

93InstallationConnecting a three−phase burner safety chain not zero volt!Please noteA jumper in the burner may possibly have to be removed from theex

Seite 163 - Keyword index

94InstallationPower supplyRegulationsCarry out the power supply connection and all earthing measures (e.g. faultcurrent circuit) in accordance with IE

Seite 164 - Keyword index (cont.)

95InstallationInstalling the control unit front5862730GB1.7.3.4.X20X105.2.6.

Seite 165

96InstallationOpening the control unit5862730GB2.1.3.

Seite 166

97CommissioningControls and display elementsA Emissions test switchB User interface:tr Boiler water temperature(N/A for multi−boilersystems)tw DHW tem

Seite 167

98CommissioningChecking the high limit safety cut−outHold down the "TÜV" test keyduring this test (position "h"). Theremust be a m

Seite 168 - Applicability

99CommissioningIntegrating the control unit into the LON system (cont.)Updating the LON user list.Only possible if all users are connected and the con

Kommentare zu diesen Handbüchern

Keine Kommentare