Subject to changes due to technical improvements ESS Energie Systeme & Service GmbH
24 CHP accessory range – 01/2010
5368 463
Electronics
6
6 Electronics
6.1 Data BUS systems / interfaces (gateway)
Article number CHP module type ESS Viessmann
for all CHP module types 710-00-0054 7411201
Function Computer connection according to requirements on site
Version Plug-in module instead of RS232 with protocol 3964
Possible interfaces • Gateway RK 512
• Gateway ProBus DP slave connection
• Gateway LON BUS connection
• Gateway CANopen connection
• Gateway MOD BUS connection
• Gateway with DK3964 R multi-module systems
Delivery Fitted in the CHP module
Note As part of order processing, the client should provide precise details about the protocol and data interface
to be set up.
6.2 Options for power failure
6.2.1 Equipment level to VDE 0108 for emergency power mode
Article number CHP module type ESS Viessmann
EM-50/81, EM-70/115, EM-140/207 710-00-0055 7411179
EM-238/363 710-00-0056 7411180
Function The module automatically recognises the power failure and disconnects from the mains.
After on-site load shedding of all consumers not eligible for emergency power, and opening of the on-site
mains coupling switch, the module can switch to emergency power. After restoration of the power supply
and a brief power steadying phase, the module is shut down and the on-site mains coupling switch is
closed. The module then runs according to standard mode.
As heat is still generated in emergency power mode, adequate provision must be made to transfer this
heat and, if necessary, supply a cooling system or buffer cylinder.
Version Equipment level for operation to VDE 0108, comprising
• Batteries to VDE 0510 part 2
• Independent battery voltage monitor
• Key switch for test run
• Key switch for power failure simulation
• Incl. conguration expenditure
• Additional zero volt message contacts for parallel mains mode and emergency power mode
Note:
The standard emergency power mode (without equipment level to VDE 0108) is included in the Vitobloc
standard delivery.
Delivery Fitted in the CHP module