System layout 9
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Arr 9
Display Channels
Channel Description Terminal Page
INIT
x*
ODB initialization active - 37
FLL
x*
ODB filling time active - 37
STAB
x*
ODB stabilization in progress - 37
COL x Temperature collector S1 37
TSTB x Temperature tank 1 bottom S2 37
TSTT x Temperature tank 1 at the top S3 37
TRET x Temperature heating circuit S4 38
n % x Pump speed relay R1 38
hP1 x Operating hours R1 R1 38
hP2 x Operating hours R2 R2 38
TIME x Time - 34
A heating circuit return preheating will be operated by
relay 2, if the temperature difference between sensors S3
and S4 is larger than or identical to the adjusted switch-on
temperature difference (DT3O). For this purpose, relay 2
will operate the 3-way-valve.